I/O List
Use I/O List to get a structured overview of signals and I/O definitions derived from the engineering model.
Treat it as the bridge between electrical design and programming/commissioning.
Workflow
Build/adjust the diagram → review I/O List for completeness → export/share.
If you see unexpected entries, check naming/metadata on the underlying objects and terminals used in the diagram.
Export
Export opens a small form. **Spreadsheet** gives Excel or CSV with the columns you pick. **TIA Portal tags** gives an Excel file to import into a PLC's tags in TIA Portal: one tag per signal with its name, data type (Bool for a digital point, Int for a 16-bit analog one), address such as %I0.0 or %IW64, and the description as the comment. Tag names come from the device and terminal (e.g. 11B3_T3) or from the description. Signals with a symbolic address, or on a device with no base address set, have no address to give TIA Portal and are left out.